Online HP3915C-S
Uninterruptible Power Supply


Specifications

• Application: Small network, servers and other IT equipment • High frequency and double conversion on-line technology • Fully digitized microprocessor control • Wide input voltage range • UPS startup without battery • Cold start • Advanced battery management • Advanced battery charge in UPS off mode • Lightning and surge protection • Short circuit and surge protection • Fan speed auto control when loads varies • Optional extension battery pack • Load capacity display • Smart RS232 communication with monitoring software • Optional SNMP Card slot
Power 15KVA / 10.5KW
Voltage range 304 ±5VAC~478 ±5VAC,
Frequency 46~54Hz ±0.5Hz, or 56~64Hz ±0.5Hz auto sensing
Input phase Three phase
Power factor 0.95
Voltage range 220VAC ±1%
Output phase Single phase
Frequency 50Hz ±0.2% (battery mode)
THD < 2% (Linear load)
Overload 105%~130% 10min turn to Bypass mode, > 130% 1s turn to Bypass mode
Crest factor 3:1 (max)
Waveform Pure sine wave
Transfer time 0ms (AC mode - Battery mode) 0ms (AC mode - Bypass mode)
Efficiency 88.00%
AC mode 5 cycles turn off inverter, no transfer to Bypass, provide alarm.
Battery mode 5 cycles turn off inverter, provide alarm.
Bypass mode Input fuse blown or break action.
Battery Model 12V sealed lead acid maintenance free
DC voltage 240VDC
Configuration External battery bank
Backup time Depends on the external battery capacity
Charge current NA (standard unit) / 5A (long time unit)
Recharge time 90% capacity after 8hrs charging
Communication Interface RS232
Parallel Port Parallel availability for redundancy and load sharing up to three unit
LCD Indication Input voltage/frequency
LED Indication Green: normal operation; Yellow: warning condition Red: abnormal operation
Noise level 55dB
Temperature 0~40ËšC
Humidity 0~95% (non-condensing)
Altitude < 1500m
Weight Net/Gross 0kg (standard unit)
Dimension (WxDxH) 320 x 620 x 950mm
Packaging (WxDxH) 410 x 720 x 1050mm
×

© 2025   |   Terms & Conditions   |   Privacy Policy   |   Site Map