Online HP3920E
Uninterruptible Power Supply


Specifications

Application: High End Servers and other critical IT equipments High frequency and double conversion on-line technology Fully digitized microprocessor control Wide input voltage range UPS startup without battery Cold start Advanced battery management Advanced battery charge in UPS off mode Lightning and surge protection Short circuit and surge protection Fan speed auto control when loads varies Optional extension battery pack Load capacity display Smart RS232 communication with monitoring software Optional SNMP Card slot
Capacity 20KVA / 14KW
Phase Three Phase in, Single Phase out
Input voltage 304 ± 5 ~ 478 ± 5 VAC
Frequency 46Hz ± 0.5 ~ 54Hz ± 0.5
Input power factor 0.95
Output voltage 220VAC ± 1%
Frequency Synchronized with AC input in AC mode
THD < 3% (linear load)
Overload capability 105% ~ 130%, alarm and go to bypass within 10min; 130% >, alarm and go to bypass within 1sec, shutdown within 1min; Recovery automatically
Crest factor 3:1 (max)
Waveform Pure sine wave
Transfer time 0 ms between AC mode & Bypass mode 0 ms between Inverter mode & Bypass mode
Efficiency 0.87 under full load
Battery Sealed lead acid
DC voltage 240VDC
Recharge time 8hours ~ 90% capacity
Charge current 5A
Parallel Up to 3 units can be parallel
Electrical protection Input/output over/under voltage, over temperature, overload, short circuit, battery low trip
Alarm Line failure, battery low, transfer to bypass & system fault
Communication interface RS232
LED indication UPS status, load or battery capacity
Noise level < 45dB
Standards EN50091-1-1 / IEC62040-2 / IEC61000-3-2 / IEC61000-3-3
Temperature 0 ~ 45ËšC
Humidity 0% ~ 95% (non-condensing)
Altitude < 1500m
Storage temperature -25 ~ 55ËšC
Weight (net / gross) 60kg / 70kg
Dimension (WxDxH) 620 x 320 x 950mm
×